![]() Dimensions shown for reference only.
RADIUS POWER www.radiuspower.com
Specifications subject to change. Standard & Custom Products PH 714-289-0055
FAX 714-289-214
Specifications
Operating Frequency: DC - 60Hz
Operating Voltage: 480V +10%
Ambient Temperature: 50
oC
Inrush Rating: 20x (10ms), 1.5x (1min)
Climatic Category: 25/100/21
Hipot Rating: 3500VDC (P/N - E)
Terminations: 15/30/35/40/45A (M5)
60/65/100A (M6)
150/200A (M10), 300A (M12)
Safety Approval: UR/cUR/EN133200
Part Number/Ordering
RP400
-X
(Amps)
-Y
(Y-cap, nF)
-T
15
0
S
30
.22
35
.47
40
1
45
2.2
60
4.7
65
10
100
22
150
100
200
1000
300
2200
Note: Use any Y (Y-cap) with any X (Amps) rating
e.g. RP400-60-100-S
60 Amps with 100nF y-caps
Leakage Current
Ycap, nF
mA, 400V/50HZ
0
0
.22
.004
.47
.009
1
.018
2.2
.04
3.3
.06
4.7
.09
10
.18
22
.4
100
1.8
1000
18
2200
30
Schematic
LINE LOAD
RP400
3PH WYE TO 300A
ROHS COMPLIANT
RP400 Series 3-Phase Wye 1-Stage Power Line
![]() Dimensions shown for reference only.
RADIUS POWER www.radiuspower.com
Specifications subject to change. Standard & Custom Products PH 714-289-0055
FAX 714-289-214
15 / 30 AMP
FREQ(MHz)
.15
.5
1
10
30
CM, dB
60
70
70
55
50
DM, dB
48
70
75
75
65
35 AMP
FREQ(MHz)
.15
.5
1
10
30
CM, dB
55
62
65
50
45
DM, dB
36
55
60
60
50
40 / 45 AMP
FREQ(MHz)
.15
.5
1
10
30
CM, dB
58
68
70
55
50
DM, dB
46
65
70
70
65
60 / 65 AMP
FREQ(MHz)
.15
.5
1
10
30
CM, dB
57
65
70
55
50
DM, dB
45
64
70
70
65
100 AMP
FREQ(MHz)
.15
.5
1
10
30
CM, dB
65
70
70
60
50
DM, dB
50
75
75
60
55
150 AMP
200 / 300 AMP
Mechanicals
FREQ(MHz)
.15
.5
1
10
30
CM, dB
55
65
60
48
40
DM, dB
50
75
70
45
45
FREQ(MHz)
.15
.5
1
10
30
CM, dB
50
50
50
45
40
DM, dB
50
45
45
40
30
I
A
B
C
D
E
F
MTG
15
4.25
3
2.75
5.5
2.5
4.85
.2x.3
30
5
4
2.75
6.7
3.25
5.8
.2x.4
35
3.9
3.3
1.75
2
3.75
---
.2x.4
40
4.25
4.25
2.25
5.75
3.5
5
.2x.4
45
7
4
3.25
8.7
3.25
7.8
.2x.4
60
8
5
3.5
10
4
9
.25x.5
65
7.25
5.5
3
8.8
4.75
8.06
.2x.4
100/150
10
6.6
4.5
12
5.12
11
.3x.6
200/300
13
6.6
4.5
15.75
5.12
14.7
.3x.6
RP400 Typical Insertion Loss, 50/50ohm
|